| Note: Click the Part Number for Specification |
| Part Number |
Description |
| FPLTC222-005 |
PROFIBUS DP Bus Cable Type A PLTC |
| FITC222-003 |
PROFIBUS DP Bus Cable Type A ITC/PLTC-ER |
| FMAR222-006 |
PROFIBUS DP Bus Cable Type A Arctic Rated |
| FAWM222-062 |
PROFIBUS DP Bus Cable Type A with PUR jacket |
Specifications and Technical Data |
PROFIBUS DP Bus Cable Type A |
ITC/PLTC - Exposed Run Rated |
 |
|
| |
|
| CABLE TYPE |
PROFIBUS DP Type A, UL Listed |
| |
ITC/PLTC - Exposed Run Rated |
| |
|
| Part Number |
FITC222-003 |
| |
|
| Physical Characteristics |
Specification |
| Geometry |
1 shielded twisted pair |
| Shield type |
65% min TC Braid over Aluminum/polyester foil - 100% coverage |
| Drain wire |
22 AWG 7 strand TC |
| Cable outside diameter |
0.435" nominal |
| Jacket marking / Agency approvals |
Northwire Inc. DataCELL® FIELD - PROFIBUS DP FITC222-003 (UL) ITC-ER 2/22 AWG 105°C E195601 Sunlight Resistant or PLTC-ER 105°C or AWM 105°C 300V or CSA CMX-OUTDOOR-CMG LL54185 105°C or CSA AWM I/II A/B 105°C 300V FT4 or IEC 332 |
| Pair Conductor size |
22 AWG 19 strand tinned copper |
| Pair Conductor OD |
0.150" nominal |
| Cable Core Diameter |
0.305" nominal |
| Colors |
red, green |
| Fillers |
extruded PVC filler rods |
| Outer Jacket material |
PVC |
| Outer Jacket color |
violet |
| Electrical Characteristics |
|
| Impedance at fr (3…20MHz) |
150 Ω nominal |
| Velocity of Propagation |
66% |
| Dielectric Withstand Voltage |
1.5kVAC |
| Maximum DC resistance (per conductor) |
52.8 Ω/km |
| |
16.1 Ω/1000ft. |
| Operating capacitance |
9.0 pF/ft. |