OnlineChatSoftware

Custom Cable Quoted Fast
No Minimum Purchase
Request Quote »

Purchase Cable Online for Immediate Delivery
Buy Online »


Northwire Express
Custom Cable Design-to-Ship in 5 Days
Read More »

NorthwireDirect
Purchase Cable Online for Immediate Delivery
Buy Online »

Custom Inventory Management
Read More »


ITC 4 WireITC PLTC

Northwire ITC-GP – Non-shielded, Non-paired

UL Listed ITC/PLTC General-Purpose

  • Also CSA CMX-Outdoor-CMG
  • High-grade black PVC outer jacket, PVC insulated conductors
  • Rugged duty cable for factory floor instrumentation and controls
  • UV and water resistant; suitable for outdoor use
  • Available factory-direct from immediate stock - no minimums
     
Part Number
AWG
No. of Conductors
Overall O.D. Inches
Nominal Insulated Conductor O.D. In.
Stranding
Fillers
Weight #/
1000 ft.
FITC223-01D
22
3
0.190"
0.050
7x.0096"TC
None
22.8
FITC224-01D
22
4
0.205"
0.050
7x.0096"TC
None
26.8
FITC225-01D
22
5
0.220"
0.050
7x.0096"TC
Poly
31.3
FITC226-01D
22
6
0.235"
0.050
7x.0096"TC
Poly
35.8
FITC203-01D
20
3
0.210"
0.059
7x.0121"TC
None
28.9
FITC204-01D
20
4
0.230"
0.059
7x.0121"TC
None
35.1
FITC205-01D
20
5
0.245"
0.059
7x.0121"TC
Poly
41.2
FITC206-01D
20
6
0.265"
0.059
7x.0121"TC
Poly
47.7
FITC183-01D
18
3
0.235"
0.070
16x30TC
None
37.2
FITC184-01D
18
4
0.255"
0.070
16x30TC
None
45.4
FITC185-01D
18
5
0.270"
0.070
16x30TC
Poly
53.6
FITC186-01D
18
6
0.305"
0.070
16x30TC
Poly
66.1

ITC 4 Wire with BraidNorthwire ITC-GP Shielded, Non-Paired

UL-listed ITC/PLTC General-Purpose with braid and foil overall shield

  • Also CSA CMX-Outdoor-CMG
  • High-grade black PVC outer jacket, PVC insulated conductors 
  • Rugged duty cable for factory floor instrumentation and controls
  • UV and water resistant; suitable for outdoor use
  • Available factory-direct from immediate stock no minimums
     
Part Number
AWG
No. of Conductors
Overall O.D. Inches
Nominal Insulated Conductor O.D. In.
Stranding
Fillers
Weight #/
1000 ft.
FITC223-02D
22
3
0.210"
0.050
7x.0096"TC
None
23.7
FITC224-02D
22
4
0.225"
0.050
7x.0096"TC
None
28.0
FITC225-02D
22
5
0.240"
0.050
7x.0096"TC
Poly
32.4
FITC226-02D
22
6
0.255"
0.050
7x.0096"TC
Poly
37.0
FITC203-02D
20
3
0.235"
0.059
7x.0121"TC
None
35.9
FITC204-02D
20
4
0.255"
0.059
7x.0121"TC
None
43.3
FITC205-02D
20
5
0.270"
0.059
7x.0121"TC
Poly
49.1
FITC206-02D
20
6
0.300"
0.059
7x.0121"TC
Poly
60.2
FITC183-02D
18
3
0.250"
0.070
16x30TC
None
42.4
FITC184-02D
18
4
0.280"
0.070
16x30TC
None
54.9
FITC185-02D
18
5
0.305"
0.070
16x30TC
Poly
66.2
FITC186-02D
18
6
0.330"
0.070
16x30TC
Poly
75.6

General Specifications  
Conductor Material Tinned Copper
Insulation Material Semi Rigid PVC to AWM 10002
Insulation Nom./Min. Thickness 0.009"/0.008"
Fillers Fibrillated Polypropylene Where Used
Inner Conductor Colors Bu, Bn, Bk, (4)Wt, (5)Gy, (6)Pk, See Color Table 1
Separator Tissue Paper
Shielded Version  
Shield Material 60% Min. 36 AWG TC Braid, 100% Mylar® Foil
Shield Type Shielded Version Braid Over Foil
Outer Jacket  
Material PVC
Color Black
Nom. Wall Thickness 0.035"
Minimum Wall Thickness 0.030"
Mechanical  
Min. Installed Bending Radius 10 x Nominal O.D.
Electrical  
Max Operating Voltage UL 300V
Dielectric Withstand Voltage 1.5kVAC
Applicable Standards and Agency Compliance
Standards  
UL UL 2250 ITC
  UL 13 PLTC
  UL AWM 2517
CSA AWM I/II A/B FT4
  CMX-OUTDOOR-CMG
  Flame Retardant FT4
  C22.2 No. 210
  C22.2 No. 214
Other IEC 332-3 Flame Rated
  Complies with NEC 725 and 727
  RoHS
Environmental and Use  
Operating Temperature Range –30°C ..+105°C
Hazardous location Class I, Div. 2
Sunlight Resistant (yes/no) Yes
Plenum/Non-Plenum Non-Plenum
Available Put-ups  
Put-Ups No Minimum Length Requirement
Continuous Lengths, Specfied Put-Ups Contact Factory