Northwire ITC-GP - non-shielded, non-paired |
| UL Listed ITC/PLTC General-purpose |
| • Also CSA CMX+Outdoor+CMG |
| • High-grade black PVC outer jacket, PVC insulated conductors |
| • Rugged duty cable for factory floor instrumentation and controls |
| • UV and water resistant; suitable for outdoor use |
| • Available factory-direct from immediate stock - no minimums |
| >> Click Here to Order from NorthwireDirect << |
Part Number |
AWG |
No. of Conductors |
Overall OD inches |
Nominal insulated conductor O.D. in. |
Stranding |
Fillers |
Weight #/1000 ft. |
FITC223-01D |
 |
22 |
3 |
0.190" |
0.050 |
7x.0096"TC |
none |
22.8 |
FITC224-01D |
 |
22 |
4 |
0.205" |
0.050 |
7x.0096"TC |
none |
26.8 |
FITC225-01D |
 |
22 |
5 |
0.220" |
0.050 |
7x.0096"TC |
poly |
31.3 |
FITC226-01D |
 |
22 |
6 |
0.235" |
0.050 |
7x.0096"TC |
poly |
35.8 |
FITC203-01D |
 |
20 |
3 |
0.210" |
0.059 |
7x.0121"TC |
none |
28.9 |
FITC204-01D |
 |
20 |
4 |
0.230" |
0.059 |
7x.0121"TC |
none |
35.1 |
FITC205-01D |
 |
20 |
5 |
0.245" |
0.059 |
7x.0121"TC |
poly |
41.2 |
FITC206-01D |
 |
20 |
6 |
0.265" |
0.059 |
7x.0121"TC |
poly |
47.7 |
FITC183-01D |
 |
18 |
3 |
0.235" |
0.070 |
16x30TC |
none |
37.2 |
FITC184-01D |
 |
18 |
4 |
0.255" |
0.070 |
16x30TC |
none |
45.4 |
FITC185-01D |
 |
18 |
5 |
0.270' |
0.070 |
16x30TC |
poly |
53.6 |
FITC186-01D |
 |
18 |
6 |
0.305" |
0.070 |
16x30TC |
poly |
66.1 |
|
|
Northwire ITC-GP shielded, non-paired |
| UL Listed ITC/PLTC General-purpose with braid and foil overall shield |
| • Also CSA CMX+Outdoor+CMG |
| • High-grade black PVC outer jacket, PVC insulated conductors |
| • Rugged duty cable for factory floor instrumentation and controls |
| • UV and water resistant; suitable for outdoor use |
| • Available factory-direct from immediate stock - no minimums |
| >> Click Here to Order from NorthwireDirect << |
Part Number |
AWG |
No. of Conductors |
Overall OD inches |
Nominal insulated conductor O.D. in. |
Stranding |
Fillers |
Weight #/1000 ft. |
FITC223-02D |
 |
22 |
3 |
0.210" |
0.050 |
7x.0096"TC |
none |
23.7 |
FITC224-02D |
 |
22 |
4 |
0.225" |
0.050 |
7x.0096"TC |
none |
28.0 |
FITC225-02D |
 |
22 |
5 |
0.240" |
0.050 |
7x.0096"TC |
poly |
32.4 |
FITC226-02D |
 |
22 |
6 |
0.255" |
0.050 |
7x.0096"TC |
poly |
37.0 |
FITC203-02D |
 |
20 |
3 |
0.235" |
0.059 |
7x.0121"TC |
none |
35.9 |
FITC204-02D |
 |
20 |
4 |
0.255" |
0.059 |
7x.0121"TC |
none |
43.3 |
FITC205-02D |
 |
20 |
5 |
0.270" |
0.059 |
7x.0121"TC |
poly |
49.1 |
FITC206-02D |
 |
20 |
6 |
0.300" |
0.059 |
7x.0121"TC |
poly |
60.2 |
FITC183-02D |
 |
18 |
3 |
0.250" |
0.070 |
16x30TC |
none |
42.4 |
FITC184-02D |
 |
18 |
4 |
0.280" |
0.070 |
16x30TC |
none |
54.9 |
FITC185-02D |
 |
18 |
5 |
0.305" |
0.070 |
16x30TC |
poly |
66.2 |
FITC186-02D |
 |
18 |
6 |
0.330" |
0.070 |
16x30TC |
poly |
75.6 |
| General Specifications |
|
| Conductor material |
tinned copper |
| Insulation material |
Semi rigid PVC to AWM 10002 |
| Insulation nom./ min. thickness |
0.009"/0.008" |
| Fillers |
fibrillated polypropylene where used |
| Inner conductor colors |
Bu, Bn, Bk, (4)Wt, (5)Gy, (6)Pk, see <color table 1> |
| Separator |
tissue paper |
| Shielded version: |
|
| Shield material |
60% min. 36 AWG TC braid, 100% Mylar foil |
| Shield type - shielded version |
braid over foil |
| Outer Jacket |
|
| Material |
PVC |
| Color |
Black |
| Nom. wall thickness |
0.035" |
| Minimum wall thickness |
0.030" |
| Mechanical |
|
| Min. installed bending radius |
10 x nominal OD |
| Electrical |
|
| Max operating voltage - UL |
300V |
| Dielectric Withstand Voltage |
1.5kVAC |
| Applicable Standards and Agency Compliance |
| Standards |
|
| UL |
UL 2250 ITC |
|
UL 13 PLTC |
|
UL AWM 2517 |
| CSA |
AWM I/II A/B FT4 |
|
CMX+OUTDOOR+CMG |
|
Flame retardant FT4 |
|
C22.2 No. 210 |
|
C22.2 No. 214 |
| Other |
IEC 332-3 flame rated |
|
Complies with NEC 725 and 727 |
| Environmental and Use |
|
| Operating temperature range |
–30°C ..+105°C |
| Hazardous location |
Class I, div. 2 |
| Sunlight Resistant (yes/no) |
yes |
| Plenum/non-plenum |
non plenum |
| Available Put-ups |
|
| Put-ups |
no minimum length requirement |
| Continuous lengths, specfied put-ups |
contact factory |