Exposed Run Power Cordage
EnduroFLEX ERP TC-Exposed Run/STOOW 600V |
||||||
Northwire Part Number |
AWG/ Conductors |
Stranding/ Cond. O.D. |
Nominal Insulation Wall Thickness |
Outer |
Cable O.D. |
Max. Current Amps |
FTC83-001 |
8/3 |
7x19x29/0.302" |
0.060" +- 0.005" |
0.110" |
0.870" |
55 |
FTC84-001 |
8/4 |
7x19x29/0.302" |
0.060" +- 0.005" |
0.125" |
1.00" |
55 |
FTC103-001 |
10/3 |
105x30/0.227" |
0.045" +- 0.005" |
0.095" |
0.680" |
40 |
FTC104-001 |
10/4 |
105x30/0.227" |
0.045" +- 0.005" |
0.095" |
0.750" |
40 |
FTC123-001 |
12/3 |
65x30/0.202" |
0.045" +- 0.005" |
0.095" |
0.625" |
30 |
FTC124-001 |
12/4 |
65x30/0.202" |
0.045" +- 0.005" |
0.095" |
0.690" |
30 |
FTC143-001 |
14/3 |
41x30/0.177" |
0.045" +- 0.005" |
0.080" |
0.545" |
25 |
FTC144-001 |
14/4 |
41x30/0.177" |
0.045" +- 0.005" |
0.080" |
0.600" |
25 |
FTC163-001 |
16/3 |
26x30/0.132" |
0.030" +- 0.005" |
0.060" |
0.410" |
18 |
FTC164-001 |
16/4 |
26x30/0.132" |
0.030" +- 0.005" |
0.060" |
0.423" |
18 |
FTC183-001 |
18/3 |
16x30/0.122" |
0.030" +- 0.005" |
0.060" |
0.390" |
14 |
FTC184-001 |
18/4 |
16x30/0.122" |
0.030" +- 0.005" |
0.060" |
0.423" |
14 |
EnduroFLEX ERP Specifications |
|
| Conductor Material |
BC – Bare Copper |
| Insulation Type/Material | 8-14 AWG: THWN-2; 16-18 AWG: TFFN PVC/Nylon |
| Conductor Colors | 1-Wh, 2-Bk, 3-Gn, 4-Rd |
| Fillers/Separator |
Paper/Tissue Paper |
| Outer Shield | Unshielded |
| Outer Jacket Material/Color |
Oil Resistant PVC/Grey |
| Operating Temperature Range | -40°C to 105°C (See UL Spec Below) |
| Max. Operating Voltage – UL |
600V RMS |
| Dielectric Withstand Voltage | 1500V AC Applied for 1 Min. *Per NEC Article 392.11 |
| NEC/UL Specification |
(UL) TC-ER 90°C Dry, 75°C Wet 600V Oil Res I & II or STOOW -40..+105°C; Sunlight Resistant, Water Resistant, UL 1277 recognized for Tray Cable – Direct Support Requirements, Complies with NFPA 79-2002 Exposed Run |
| UL Flame Test/CSA Flame Test | Meets UL Vertical Tray/FT-4 |