EnduroFLEX ERP TC-Exposed Run / STOOW 600V |
Northwire
Part Number |
AWG/
Conductors |
Stranding/
cond. OD |
Nominal insulation
wall thickness |
Outer
jacket wall |
Cable
O.D. |
Max. Current
Amps |
FTC83-001 |
8/3 |
7x19x29/0.302" |
0.060" +- 0.005" |
0.110" |
0.870" |
55 |
FTC84-001 |
8/4 |
7x19x29/0.302" |
0.060" +- 0.005" |
0.125" |
1.00" |
55 |
FTC103-001 |
10/3 |
105x30/0.227" |
0.045" +- 0.005" |
0.095" |
0.680" |
40 |
FTC104-001 |
10/4 |
105x30/0.227" |
0.045" +- 0.005" |
0.095" |
0.750" |
40 |
FTC123-001 |
12/3 |
65x30/0.202" |
0.045" +- 0.005" |
0.095" |
0.625" |
30 |
FTC124-001 |
12/4 |
65x30/0.202" |
0.045" +- 0.005" |
0.095" |
0.690" |
30 |
FTC143-001 |
14/3 |
41x30/0.177" |
0.045" +- 0.005" |
0.080" |
0.545" |
25 |
FTC144-001 |
14/4 |
41x30/0.177" |
0.045" +- 0.005" |
0.080" |
0.600" |
25 |
FTC163-001 |
16/3 |
26x30/0.132" |
0.030" +- 0.005" |
0.060" |
0.410" |
18 |
FTC164-001 |
16/4 |
26x30/0.132" |
0.030" +- 0.005" |
0.060" |
0.423" |
18 |
FTC183-001 |
18/3 |
16x30/0.122" |
0.030" +- 0.005" |
0.060" |
0.390" |
14 |
FTC184-001 |
18/4 |
16x30/0.122" |
0.030" +- 0.005" |
0.060" |
0.423" |
14 |
EnduroFLEX ERP Specifications |
Conductor Material
|
BC–Bare Copper |
| Insulation Type / Material |
8-14 AWG: THWN-2; 16-18 AWG: TFFN PVC / Nylon |
| Conductor Colors |
1-Wh, 2-Bk, 3-Gn, 4-Rd |
Fillers / Separator
|
Paper / Tissue paper |
| Outer Shield |
Unshielded |
Outer Jacket Material / Color
|
Oil resistant PVC / Grey |
| Operating Temperature Range |
–40°C to +105°C (see UL spec below) |
Max. Operating Voltage–UL
|
600V RMS |
| Dielectric Withstand Voltage |
1500V AC applied for 1 min. *per NEC article 392.11 |
NEC / UL Specification
|
(UL) TC-ER 90°C dry, 75°C wet 600V Oil res I & II or STOOW -40..+105°C; sunlight
resistant, water resistant, UL 1277 recognized for Tray Cable - direct support
requirements, Complies with NFPA 79-2002 Exposed Run
|
| UL Flame Test/ CSA Flame Test |
Meets UL Vertical Tray / FT-4 |