EnduroFLEX ERP exampleEnduroFlex ERP
Exposed Run Power Cordage

EnduroFLEX ERP TC-Exposed Run/STOOW 600V

Northwire
Part Number
AWG/
Conductors
Stranding/
Cond. O.D.
Nominal Insulation
Wall Thickness

Outer
Jacket Wall

Cable
O.D.
Max. Current
Amps
FTC83-001
8/3
7x19x29/0.302"
0.060" +- 0.005"
0.110"
0.870"
55
FTC84-001
8/4
7x19x29/0.302"
0.060" +- 0.005"
0.125"
1.00"
55
FTC103-001
10/3
105x30/0.227"
0.045" +- 0.005"
0.095"
0.680"
40
FTC104-001
10/4
105x30/0.227"
0.045" +- 0.005"
0.095"
0.750"
40
FTC123-001
12/3
65x30/0.202"
0.045" +- 0.005"
0.095"
0.625"
30
FTC124-001
12/4
65x30/0.202"
0.045" +- 0.005"
0.095"
0.690"
30
FTC143-001
14/3
41x30/0.177"
0.045" +- 0.005"
0.080"
0.545"
25
FTC144-001
14/4
41x30/0.177"
0.045" +- 0.005"
0.080"
0.600"
25
FTC163-001
16/3
26x30/0.132"
0.030" +- 0.005"
0.060"
0.410"
18
FTC164-001
16/4
26x30/0.132"
0.030" +- 0.005"
0.060"
0.423"
18
FTC183-001
18/3
16x30/0.122"
0.030" +- 0.005"
0.060"
0.390"
14
FTC184-001
18/4
16x30/0.122"
0.030" +- 0.005"
0.060"
0.423"
14

EnduroFLEX ERP Specifications
Conductor Material
BC – Bare Copper
Insulation Type/Material 8-14 AWG: THWN-2; 16-18 AWG: TFFN PVC/Nylon
Conductor Colors 1-Wh, 2-Bk, 3-Gn, 4-Rd
Fillers/Separator
Paper/Tissue Paper
Outer Shield Unshielded
Outer Jacket Material/Color
Oil Resistant PVC/Grey
Operating Temperature Range -40°C to 105°C (See UL Spec Below)
Max. Operating Voltage – UL
600V RMS
Dielectric Withstand Voltage 1500V AC Applied for 1 Min. *Per NEC Article 392.11
NEC/UL Specification
(UL) TC-ER 90°C Dry, 75°C Wet 600V Oil Res I & II or STOOW -40..+105°C; Sunlight Resistant, Water Resistant, UL 1277 recognized for Tray Cable – Direct Support Requirements, Complies with NFPA 79-2002 Exposed Run
UL Flame Test/CSA Flame Test Meets UL Vertical Tray/FT-4