| Cable Type |
DeviceNet Thick PLTC Cable |
| Version |
ODVA Thick PLTC AWM |
| Part Number |
FPLTC154C-001 |
| Network Standard |
ODVA DeviceNet |
|
Data Pair Specifications
|
| Physical Characteristics |
Specification |
| Conductor Pair Size |
18 AWG 19 Strand TC |
| Insulation Diameter |
0.135 ± .005" |
| Colors |
Bu, Wh |
| Pair Twist/ft. |
Approx. 3 |
| Tape Shield Over Pair |
Al/Polyester Foil Out w/Shorting Fold (Pull-on Applied) |
| Electrical Characteristics |
Specification |
| Impedance |
120Ω ± 10% |
| Propagation Delay |
1.36 ns/ ft. (nom) |
| Capacitance Between Conductors |
10.75pF/ ft @ 1KHz |
| Capacitance Between One Conductor and Other Conductor Connected to Shield |
24pF/ ft @ 1KHz |
| Capacitive Unbalance |
1200 pF/ 1000 ft. Maximum |
| DCR – @ 20° C |
7.06 Ω /1000 ft. |
| Attenuation |
@ 125 kHz: 0.049 dB/100ft. |
| @ 250 kHz: 0.049 dB/100ft. |
| @ 500 kHz: 0.049 dB/100ft. |
| @ 1 MHz: 0.049 dB/100ft. |
|
DC Power Pair Specifications
|
| Physical Characteristics |
Specification |
| Conductor Pair Size |
15 AWG 19 Strand TC |
| Insulation Diameter |
0.098 ± .002" |
| Colors |
Rd, Bk |
| Pair Twist / ft. |
Approx. 3 |
| Tape Shield Over Pair |
Al/Polyester Foil Out w/Shorting Fold (Pull-On Applied) |
| Electrical Characteristics |
Specification |
| DCR – @ 20° C |
3.6 Ω /1000 ft |
|
General Specifications
|
| Physical Characteristics |
Specification |
| Geometry |
2 Shielded Pairs, Common Axis w/Drain Wire in Center |
| Overall Braid Shield |
65% Minimum 36 AWG TC |
| Drain Wire |
18 AWG 19 Strand TC |
| Outside Diameter |
0.440 ± .010" " |
| Roundness |
Radius Delta Less Than 15% of 1/2 O.D. |
| Jacket Marking |
Northwire Inc. DataCELL FIELD DeviceNet Thick – FPLTC154C-001 (UL) 15AWG/2 18AWG/2 PLTC 75°C E90625 or AWM 80°C 600V or CSA AWM LL54185 I/II A/B 80°C 600V FT4 |
| Electrical Characteristics |
Specification |
| DCR (Braid+Tape+Drain) |
1.75 Ω /1000 ft.Nominal @ 20°C |
| Applicable Environmental Characteristics |
Specification |
| Agency Certifications (US and Canada) |
NEC (UL) Type PLTC or AWM; CSA AWM
(Note: PLTC Supercedes CL2 and CL3 per NEC 725.61) |
| Flexure |
Tested 2000 Cycles Minimum at 4.5 Bend Radius 90 Degrees 2 lb. Minimum Pull Force, 30 Cycles Per Minute, Tick-Toc Method |
| Bend Raduis |
20 x Diameter (Installation); 7 x Diameter Fixed) |
| Operating Ambient Temperature |
-20..75° |
| Storage Temperature |
-40..85°C |
| Pull Tension |
190 lb. Maximum |
| Connector Compatibility |
Mini, Open |
| Topology Compatibility |
Trunk, Drop |